Smart Electronic Components Procurement
| |

4MM DIN RAIL FUSE TERMINAL 6.3A BLACK


SKU: DC4-HE-BLACK

Availability:

948 in stock (can be backordered)

  • MPN: DC4-HE-01P-13-00Z(H)
  • Manufacturer: Degson
  • Pack Size: 50 Box

$2.50 Exc GST

Qty Price Per Unit Total Price
1+ $2.75 Incl GST $2.50 Excl GST $2.75 Incl GST $2.50 Excl GST
100 $2.20 Incl GST $2.00 Excl GST $220.00 Incl GST $200.00 Excl GST

Fused DIN Rail Terminal rated at 600v and 6.3A. This fuse holder will accept metric M205 cartridge fuses.

  • Fuses are supplied separately and are not included.

 

DC4-HE-BLACK Datasheet

Category Specification
Overview
Number of rows 1
Number of connections 2
Open-end side panels Yes
Insulation Materials PA
Flame retardant grade V0 (UL 94)
Insulating material group I
Standard test IEC60947-7-3
Fuse G/5 x 20
Fuse type Glass/Ceramic/…
Connection method Screw connection
Dimensions
Width 8mm
End plate width 1.5mm
Height 46.5mm
NS 35/7,5 Height 48mm
NS 35/15 Height 55.5mm
Length 58mm
Wiring Data
Strip length 8~9mm
Conductor cross section (solid AWG) 22~10
Conductor cross section (solid) 0.5~6mm²
Conductor cross section (flexible) 0.5~4mm²
Conductor cross section (ferrule without plastic sleeve) 0.5~4mm²
Conductor cross section (ferrule with plastic sleeve) 0.5~2.5mm²
2 flexible conductors with a TWIN ferrule 0.5~1.5mm²
Screw type Slotted screw
Screw thread M3
Tightening torque 0.6 N.m
IEC Electrical Parameters
Rated voltage (III / 3) 500V
Rated current (III / 3) 6.3A
Rated surge voltage 6kV
UL Electrical Parameters
Rated voltage 600V
Rated current 6.3A
Environmental Conditions
Ambient temperature (operation) -40°C ~ 105°C (depending on derating curve)
Relative humidity (storage/transport) 25%~75%
Ambient temperature (storage/transport) -25°C ~ 60°C
Mechanical Performance Test
Mechanical strength Passed the test
Fixing support Passed the test
Rotational pull test Passed the test
Electrical Performance Test
Voltage drop ≤3.2mV
Temperature rise test ≤45 K
Safety Test
Anti-finger touch Passed the test
Environmental Protection
RoHS No excessive harmful substances
REACh SVHC Lead 7439-92-1